Rated supply voltage |
120 – 277 V |
AC voltage range |
108 – 305 V |
Rated current (at 120 V, 60 Hz, full load) |
0.95 A |
Rated current (at 277 V, 60 Hz, full load) |
0.45 A |
Leakage current (at 120 V, 60 Hz, full load) |
< 500 µA |
Leakage current (at 230 V, 50 Hz, full load) |
< 500 µA |
Mains frequency |
50 / 60 Hz |
Efficiency (at 120 V 60 Hz, full load) |
> 88 % |
Efficiency (at 277 V 60 Hz, full load) |
> 90 % |
λ (at 120 V, 60 Hz, full load) |
0.98 |
λ (at 277 V, 60 Hz, full load) |
0.95 |
Typ. power input on stand-by (at 120 V, 60 Hz) |
< 0.7 W |
Typ. power input on stand-by (at 277 V, 60 Hz) |
< 0.5 W |
Typ. input current in no-load operation (at 120 V, 60 Hz) |
50 mA |
Typ. input current in no-load operation (at 277 V, 60 Hz) |
37 mA |
Typ. input power in no-load operation (at 120 V, 60 Hz) |
0.75 W |
Typ. input power in no-load operation (at 277 V, 60 Hz) |
0.57 W |
Output voltage tolerance |
23.5 – 24.5 V |
Max. output power |
99.6 W |
Output power range |
0.1 – 99.6 W |
Output LF current ripple (< 120 Hz, P-P) |
< 1,000 mV |
Starting time (output) |
≤ 500 ms |
Turn off time (output) |
≤ 10 ms |
Hold on time at power failure (output) |
≤ 1 ms |
THD (at 120 V, 60 Hz, full load)
(1) |
< 10 % |
THD (at 277 V, 60 Hz, full load)
(1) |
< 20 % |
Mains burst capability (between L - N) |
1 kV |
Mains surge capability (between L - N) |
2 kV |
Mains surge capability (between L/N - PE) |
4 kV |
Surge voltage at output side (against PE) |
< 500 V |
Ambient temperature ta |
-40 ... +131 °F |
Ambient temperature ta (at life-time 50,000 h) |
113 °F |
Storage temperature ts |
-40 ... +185 °F |
Life-time |
up to 50,000 h |
Dimensions L x W x H |
9.5 x 1.69 x 1 inch |
Hole spacing D |
0.25 inch |